I see from another post that its a Alpha CB24 which has a minimum output of 9.3kw and a max of 23.3kw.
All gas boilers fire up at ~ 60% of max output, in your case, say 14kw, the boiler should then modulate to maintain its SP...
Thanks so I rang technical they told me to do a test on the divertor valve. I thought this would only possibly cause a problem with the hot water. But they said it can cause both to cycle. Unsure why it settles when hot though. Will try...
Thanks. With regards to point A. Once hot it doesn't cut out on hot water. I'm correct in saying the boiler doesn't modulate down in hot water mode is always on max? But very good points
Assuming it's a gas boiler, I have two guesses:
(a) when the system is cold the boiler tries to run at 24kW and cycles due to lack of circulation but once everything is warm it modulates down to a level that the circulation rate copes...
Any ideas what could cause a boiler to repeatedly cycle on and off on both hot water and central heating. Until the boiler gets to temperature then settles down and stays on for both.
Any idea how they make sure it's going through the plate when put in the filling loop? As running the hot tap will divert the water that is presently in the heat exchanger around the plate. Run heating for a second before. Running the...
Do they use method where you can syphon the clearer in to the main hex? Obviously closer to the plate then. Or just add the cleaner to a radiator/filling loop
If putting this in a system would it at all help clean a plate heat exchanger if repeatedly turning the hot tap on so the C/H water runs through the plate? I imagine not or everyone would so it instead of taking the plate out.
Thanks
Thanks means 2 less compression joints on an outside tap installation. I don't think many merchants stock them ? Haven't asked yet but just seem online
Hi just to confirm does this look like a rigid syphon. Not seen in person but doesn't look like it one of the ones that splits so can replace the diaghram. Thanks
If I take the cistern off and take the syphon out would any 1.5inch syphon washer fit to seal it. It's leaking through the seal were the syphon sits on the cistern. Tried tightening in place no look.
Has anyone fit inline expansion valve on the cold water supply to an unvented cylinder. The normal style were you just tee of after the composite valve can leave a dead leg in the pipework? A local water authority has pulled some. Thanks