Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Rf cylinder stat? Has anyone used one are they good? in the Plumbing Jobs | The Job-board area at Plumbers Forums

Millsy 82

Plumbers Arms member
Plumber
Gas Engineer
Messages
4,350
I have a job at a b&b that the water is apparently getting scalding. It has an old oil boiler and the hot water is on gravity. I've been out before and the cylinder has been changed not too long ago and has not been installed brilliantly.

My only thought is to convert it to fully pumped but getting a wire back from the cylinder could prove an absolute nightmare. So quick Google and I've found a few rf cylinder stats has anyone used one before? Are they any good?

This also may not work as I can't remember where the cold feed and vent go into the system so I may not be able to convert it if the feed and vent go into the f&r for the cylinder.
 
One of these maybe an idea for gravity just make sure there's a heat sink rad

Screenshot_20190509-091945_Samsung Internet.jpg
 
One of these maybe an idea for gravity just make sure there's a heat sink rad

View attachment 38551


Hello Steve weightman,

The Danfoss Hot Water Cylinder Thermostatic Valve might be a good suggestion for the OP`s requirements if as He mentions there is an additional `Heat Sink` Radiator and the Feed & Vent pipework on the system will allow or could be altered to suit fitting it.

But - what a price for something that is not much more complicated or expensive to manufacture than a 22mm TRV with a remote sensor probe !

That is an example of a product where the fact that it negates the requirement for a Hot Water Cylinder Zone Valve and the associated Electrical wiring / Electrical thermostat allows the price to be vastly inflated well over the cost of manufacture / manufacturers profit and suppliers overheads / profit.

I know that the Danfoss valve can be bought for less money but still usually way over £120.00.

Obviously in situations such as the OP describes these prices might still be actually be cost effective / easily justifiable compared to other alternatives.

Having written that - a RF Cylinder Thermostat can cost quite a lot more than that and would still require that a Zone Valve was installed for the Cylinder which would have to be wired up - but possibly close to the Boiler ?

Chris
 
Last edited:

Similar plumbing topics

K
  • Question
Or, the electric shower can be replaced with a...
Replies
2
Views
1K
  • Question
Thank you John, will give that a try as well 👍
Replies
14
Views
4K
  • Question
Yours is an old fotic cylinder, Thermal store...
Replies
1
Views
982
Back
Top