Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Communal heating. in the Plumbing Jobs | The Job-board area at Plumbers Forums

spanner

Plumbers Arms member
Plumber
Gas Engineer
Messages
1,237
Had a customer call today about low water pressure and sent a pic of the installation.
Obviously get these by the dozens.
Surprisingly turn up to an old 1970s communal heating system that's pitting and degrading gradually.
Whats this system if anyone recognises it.
Thing is I think it's a one pipe return. But
IMG_20190805_173103.jpg
.
Questions
Is it possible to isolate the district heating and install own controls,??
Doable??
 
Yes, I have done a couple & have a 3rd to do next week but it is fraught with danger.
Do they own the property ?
What are the isolation valves like? as they will be the only thing holding back a lot of primary heating water.
 
Yes, I have done a couple & have a 3rd to do next week but it is fraught with danger.
Do they own the property ?
What are the isolation valves like? as they will be the only thing holding back a lot of primary heating water.
Never took a pic. Dominator on return "I think"Will do later this week as the initial call was for low water pressure at thd hot cold bath basin outlet and no pressure when shower attachment goes up little above bath height.
To my surprise to find they'd just bought the place and I discover district heating and to operate heating / hot water are two lever valves. A radiator trv attached to control hot water which then when satisfied stops the back around the circuit.
Anyone familiar with this.
As I'm thinking adding additional controls and wiring system won't work. May plug for a while but would need to seek info.
Any help appreciated..
 

Attachments

  • IMG_20190805_173113.jpg
    IMG_20190805_173113.jpg
    3.3 MB · Views: 10
  • IMG_20190805_180625.jpg
    IMG_20190805_180625.jpg
    2.9 MB · Views: 10
  • IMG_20190805_173103.jpg
    IMG_20190805_173103.jpg
    3.8 MB · Views: 10
I have Megaflo's installed (by others) where the district heating pumps are pushing past the Honeywell 2 ports causing the cylinders to overheat.
I takes over a Bar in pump pressure to do that I found out.
I'll probably never come across systems like this, but in that scenario would it be better to seperate the systems through a plate heat ex so you don't get the pressure forcing water through the zone valve?
 
Seen it all the time. Just what's the point of just adding a universal hot cold pump to boost bathroom for showers when this!!
This is a first I've seen on an old district heat system.
 
I'll probably never come across systems like this, but in that scenario would it be better to seperate the systems through a plate heat ex so you don't get the pressure forcing water through the zone valve?
That was one of my first suggestions but the cost was great, it wasn't just the cost of the HIU but that the places would need to be re-piped. Most of the rad's are 80's style (non convector) sized for 80deg C water, so very small, there would be a resulting loss of temperature with exchange (estimated +10 C).
The contract with the energy supplier is such that they (the supplier) are still responsible for the isolation & rad valves.
All in all pressure controls was the better option, so far, been in 2 years now.
 
On purchase of the dwelling the buyer was given a handbook of notices and numbers I've been told. Will investigate later on.
As for heating isolation before touching any primaries ill have to see what the measure is before going any further.
What's funny is the tenant is more bothered of the low water pressure in bathroom than the current state of the system. Quite easy to add the booster but again see how far things go 1st
 
What's funny is the tenant is more bothered of the low water pressure in bathroom than the current state of the system. Quite easy to add the booster but again see how far things go 1st
Nothing unusual there then!!
Personally I would not like to just fit a booster pump to a Harcopak as it will more than likely draw in air.

BTW the TRV is what they call a Tapstat works in a similar way to a remote TRV to control the HW temp with out electrical controls. https://www.draytoncontrols.co.uk/sites/all/modules/custom/drayton_catalogue/files/assets/common/downloads/DRAYTON Product Catalogue.pdf
 

Similar plumbing topics

What he said. Looks like 15mm copper conns...
Replies
7
Views
2K
P
Hi, I have a new built house with the...
Replies
0
Views
955
PierpaoloB
P
Thanks, I shall take a look in that case and...
Replies
21
Views
3K
    • Like
Great summary and well done for getting it...
Replies
1
Views
2K
J
We’ve had a UFH system installed as part of...
Replies
0
Views
2K
JSlippy
J
Back
Top