Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Problems with Honeywell Evohome system in the Central Heating Forum area at Plumbers Forums

LRC

Messages
8
Hi, I’m looking for advice about our Honeywell Evohome system. It has never been quite right & looking at info online I think the BDR91s have been installed too close together. At the moment we have a problem with the hot water connection - on the base unit it is just showing an egg timer rather than a temperature & we are unable to get it to connect so we will be running out of hot water soon. Any advice appreciated! Thank you
 

Attachments

  • A6AB38FC-E3FA-4EA6-9B41-14754A917B63.jpeg
    A6AB38FC-E3FA-4EA6-9B41-14754A917B63.jpeg
    130.6 KB · Views: 27
the stopwatch sign on hot water is temporary override
The stop watch sign isn't the override. It's the symbol when it's lost communication with the HW receiver.

HW sensor - needs good AA batteries that are reading over 1.5v. Soon as they drop below 1.5v they play up. So replace the batteries then press the button on the front once. If that doesn't solve the issue there are other things it can be.

Regarding the other issues bit of background/problems might help address these.
 
The stop watch sign isn't the override. It's the symbol when it's lost communication with the HW receiver.

HW sensor - needs good AA batteries that are reading over 1.5v. Soon as they drop below 1.5v they play up. So replace the batteries then press the button on the front once. If that doesn't solve the issue there are other things it can be.

Regarding the other issues bit of background/problems might help address these.

Thank you! It was a problem with the batteries (we didn’t even know it had batteries:oops:)
It all seems to be working fine now, thanks so much for your help!
 
According to this it is it’s all I can go off
Sorry I thought you were referring to the egg timer, I didn’t see the stopwatch in the corner.

Yes the stopwatch means a override has taken place by the user.

The egg timer means there’s an issue with communication between the panel and the CS92A
 
Sorry I thought you were referring to the egg timer, I didn’t see the stopwatch in the corner.

Yes the stopwatch means a override has taken place by the user.

The egg timer means there’s an issue with communication between the panel and the CS92A
It’s ok I didn’t notice the egg timer 😀 never dealt with evohome only had 1 customer with it
 

Similar plumbing topics

Thanks for the reply whats the best suggestion...
Replies
2
Views
1K
P
Hi, I have the same issue. I have unbinded...
Replies
1
Views
2K
kristola
K
  • Question
Yes it was the batteries which we didn’t even...
Replies
2
Views
4K
The timeclock is hopefully fairly self...
Replies
3
Views
574
Back
Top