Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss What does the internal bypass valve do in a Viessmann combi? in the Central Heating Forum area at Plumbers Forums

Messages
40
Could someone please explain what is the function of the internal bypass valve in a Viessmann combi and how its settings MIN/MAX or malfunction somehow would affect operation of DHW and heating?
Thanks in advance.
 

Attachments

  • Screen Shot 2021-12-12 at 14.46.36.png
    Screen Shot 2021-12-12 at 14.46.36.png
    196.1 KB · Views: 53
When the boiler switches from hot water to heating the water moving has to go somewhere when the diverter switches over
 
It’s set to x pressure so when the diverter moves the system increases pressure and the bypass activates
 
Should be set so under normal operation it doesn’t open
 
The MIN pressure seems to be around 140 mbar. But what ist the opening pressure in the MAX position? I cannot find this information anywhere.
 
Vaillant have a internal bypass ( on the primary circuit) on all their system and combi boilers, it is factory set to 250mar but is adjustable from a minimum of 170mbar to a max of 350mbar, it provides the minimum flowrate required by the boiler at reduced flow demand and pump overrun after boiler shutdown, Viessmann setting may be similiar.
 

Similar plumbing topics

Modern boilers are designed to cycle once the...
Replies
3
Views
563
Everything working fine on PP mode - thanks...
Replies
7
Views
916
If the op has the newer colour display model...
Replies
5
Views
3K
I would set the internal bypass to its max...
Replies
10
Views
2K
Hi d36csr. You aren't a bicycle plumber are...
Replies
11
Views
3K
Back
Top