Fully pumped CH systems? Potterton Profile 80e conventional boiler. | Boilers | Plumbers Forums
  • Welcome to PlumbersTalk.net

    Welcome to Plumbers' Talk | The new domain for UKPF / Plumbers Forums. Login with your existing details they should all work fine. Please checkout the PT Updates Forum

Welcome to the forum. Although you can post in any forum, the USA forum is here in case of local regs or laws

American Visitor?

Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Fully pumped CH systems? Potterton Profile 80e conventional boiler. in the Boilers area at Plumbers Forums

Messages
2
AFAIK the boiler is set to fully pumped. (The switch inside is on fully pumped), however the pump is only running while the boiler burner is actually lit.

My understanding is that a fully pumped system should have the pump running for a while after the burner goes off to circulate the heated water around.

Looking at the boiler diagrams, there is a pump over run thermostat that is used when set for fully pumped, which keeps the pump running until the heat exchanger temp drops below 80c.

This stat is fed from a terminal marked Switched Live. On this installation, the Switched Live terminal goes up to the main terminal box but is not connected to anything! I assume it's supposed to go to a room stat or something?

The manual says to connect it to permenant live if there is no 'external control' fitted.

Is there any reason why this would not have been wired up? Should the pump actually run for a period after the burner shuts off?

The rads take a while to warm up and if the HW or UFH circuits are off, they take forever to warm up. I am thinking that this is because the pump isn't over running.
BOILER cicuit.jpg
BOILER cicuit.jpg
BOILER cicuit.jpg
 

Similar plumbing topics

Very informative...........thx🙄
Replies
3
Views
574
Are you controlling the stove flow temperature...
Replies
6
Views
1K
Just happened to be rummaging around on the...
Replies
10
Views
3K
Hi, thanks for the reply, that did cross my...
Replies
2
Views
820
    • Like
Great summary and well done for getting it...
Replies
1
Views
2K
Back
Top