Is there a flexible pipe suitable for a secondary hot water circulatory system? | UK Plumbers Forums | Plumbers Forums
  • Welcome to PlumbersTalk.net

    Welcome to Plumbers' Talk | The new domain for UKPF / Plumbers Forums. Login with your existing details they should all work fine. Please checkout the PT Updates Forum

Welcome to the forum. Although you can post in any forum, the USA forum is here in case of local regs or laws

American Visitor?

Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Is there a flexible pipe suitable for a secondary hot water circulatory system? in the UK Plumbers Forums area at Plumbers Forums

Messages
33
I'd be grateful for some advice please.
I'm doing a stable conversion which requires a secondary circulatory system. The plumber (yes, he is qualified) initially didn't realise this and when questioned, didn't actually appear to know what a secondary system was! He did come back to install one though, but I've now discovered (just in time before the ceilings are boarded over), that the pipework he's fitted, using JG flexible pipe and fittings, is unsuitable for a secondary circulatory system. Replacing his runs in solid copper is going to be a nightmare because part of the system passes through I beams (so will involve lots of short lengths joined together). Does anyone know of a flexible pipe which would be suitable for a secondary hot water system so I can just pull it through to replace the JG stuff?
Thankyou in anticipation.
 
Mlcp is fine for src
 
Thanks Shaun. I was hoping it would be.

Just make sure it’s double / thick insulated min 25mm

Mlcp is all the best bits of copper in a flexible form
 
Solution
My theory is that Polypipe claim their pipe isn't suitable, presumably from reading the literature because they don't want the pipework/fittings to remain at high temperatures continuously. They do say that even timer/thermostat controlled systems aren't suitable but I personally think they've just said that as a precaution. Or that there is something they can't achieve to get the suitable British standard

The same pipe is used to carry 80*c water for heating systems for long periods of time so I can't see how leaving a secondary return on for let's say 4 hours at 60*c in the evening would cause any damage.

Having said that. I'm extremely risk averse so wouldn't try it at a customers expense but would definitely setup a jig to try it if I can get my hands on some old/spare parts
 
My theory is that Polypipe claim their pipe isn't suitable, presumably from reading the literature because they don't want the pipework/fittings to remain at high temperatures continuously. They do say that even timer/thermostat controlled systems aren't suitable but I personally think they've just said that as a precaution. Or that there is something they can't achieve to get the suitable British standard

The same pipe is used to carry 80*c water for heating systems for long periods of time so I can't see how leaving a secondary return on for let's say 4 hours at 60*c in the evening would cause any damage.

Having said that. I'm extremely risk averse so wouldn't try it at a customers expense but would definitely setup a jig to try it if I can get my hands on some old/spare parts
Thanks for the comments fowlerboi. Like you I can't see any justification for not using it but don't want to experiment in case it does go pear shaped. At least I can use the existing holes with MCLP so it's not all bad.
 

Similar plumbing topics

B
  • Question
Well, I'm thinking if your HOT OUT goes in a...
Replies
14
Views
2K
  • Question
This issue arose about a year ago. Does anyone...
Replies
0
Views
653
  • Question
Definitely worth checking the clipping...
Replies
1
Views
640
  • Question
Hi there, We have a standard gravitational...
Replies
0
Views
883
  • Question
Hi Hi if you have a expansion pipe if must...
Replies
15
Views
2K
Back
Top