Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Underfloor heat pipe specification and pipe centres and radius bends. in the UK Plumbers Forums area at Plumbers Forums

P

Paul GG

In my attempt to future proof my underfloor heating design to maximise the heat output at the lowest possible mean water temperature, I am planning pipe 16mm dia pipe centres at 133mm governed by the nature of the installation (3 pipes per space between floor supports at 400 mm ctrs. - Serpentine layout.
I would welcome any advice on the best possible pipe spec or brand for this approach so alleviate any issues with bend radius on the pipe.

My second option is to move to a 200mm pipe centre layout scenario ( 2 pipe per space between floor support at 400 mm ctrs. Again any advice on the best possible pipe spec or brand would be appreciated.

The concluding question is the heat output gain via 133mm pipe centres again 200mm pipe centres ,at the same mean water temperature is difficult to calculate ref differing floor constructions . Maybe the simple answer here is to raise the mean water temperature a few degrees under the 200mm pipe centre option to achieve same output of the 133mm pipe centre option.

hope all this make sense , and any advice from practical experience would be much appreciated.
 
Sorry , the floor supports are 50mm wide ( 350mm space between supports) some like the photo attached. The plywood on top of the floor joists as per the photo would a cement board to improve heat efficiency ( heat sink)
 

Attachments

  • 1719600295712.png
    1719600295712.png
    520 KB · Views: 23
Smaller centres = lower heat input temp
Bigger centres = higher heat input temp
 
Have fitted a vast amount of differing systems and all 15/16mm pipes I've ever used have a rough bend radius of 200mm. If you were to go down the route of 130mm centers you would need to stagger to bends to form a sort of bell shaped turn.
 
You talk about floor supports, what are they and what are their dimensions?
400 centres does not give 400mm between supports unless they have zero thickness!
Sorry , the floor supports are 50mm wide ( 350mm space between supports) some like the photo attached on original thread . The plywood on top of the floor joists as per the photo would a cement board to improve heat efficiency ( heat sink)

Attachments​

 
Thanks Shaun, any advice on pipe spec in relation of achieve the bend radius with ease without any possibility of kinks etc. thanks

You can do 120mm centres easily with mlcp you can do 100mm centres with a bending spring / bender
 

Similar plumbing topics

  • Question
Hi, I have I blend valve from Nu-Heat ( they...
Replies
0
Views
667
  • Question
We currently have the ground floor wet UFH and...
Replies
0
Views
827
  • Question
https://www.bes.co.uk/electric-hockey-stick-bla...
Replies
8
Views
3K
I have connected the secondary pump to a wifi...
Replies
9
Views
2K
H
Hi there, thanks for your time to look at this...
Replies
0
Views
856
HRP123
H
Back
Top