Not much general plumbing experience.
Mains stopcock handle sheared off. Street isolation only outside for 4/5 houses.
So to save any faffing about was just going replace spindle.
Question is do all stopcocks have same size spindle and gland thread?
Recently purchased a house. One of the selling points was a hardly used year old heating system installed by Scottish Gas.
After a week I noticed a drop in pressure so decided I better get this sorted before moving in.
I found most of the 30 year old back boiler system still in place including a...
Was at service of Back boiler earlier and this is what found in loft.
Got the usual comment of "In 15 years no one has ever been up my loft to check anything".
What ye all think?
(why do these pics rotate when added)
Trying get my head around this one.
Worcester 28i RSF (twin pass heat exchanger) is heating rads when running hot tap. Other Engineers have just told customer to turn down TRV's. Not a fix for the problem as bypass rad still heats.
Any ideas?
Check valves on flow and return bellow boiler maybe?
Called to an 18 month old Vision 30C earlier with poor hot water. Hot water luke warm at best showing a max of 35 deg on boiler display. If slow tap to little more than a trickle the temp gets up around 60 deg eventually. No issues with heating.
Boiler fitted to an old back boiler heating system...
Was at one these Syntesi boilers tonight.
Have ignition and burner goes to high flame for about 3 seconds then goes to 01 flashing red lockout.
Checked wireing/connections etc. and gas is ok.
Rectification? PCB issue maybe?
Thoughts on this set up guys.
A load of these installs have appeared on my patch.
Prv ran into condensate pump via tundish and plastic pipework.
The condensate pump is compatible as per Saermann.
Vokera were giving no specific answer saying refer to British Standards.
Wee bit of help please.
Last job of evening. No hot water.
Never come across this pile of junk. It's like the budget version of a budget boiler. Branded 'FER'. Its 5 yr old and looks like its at least 15yr old due to multiple leaks/issues previously.
It has a plate hex, divertor motor and hot...
Just been looking at the above for neighbour.
Alternate light A & B flashing. Pump runs. Continuity through low water switch. Thermistors etc ok. APS open circuit.
No power to fan.
Thinking got to be the board?
Thoughts people?
Lay down the scene:
15yr old Worcester 28CDi hemed into upstairs airing cupboard with about 50mm to sides and 150mm below boiler.
One burst expansion vessel with no reasonable option to fit a remote replacement.
One replacement vessel ordered up.
About 4hrs after removing pump, plate heat...
More a question for the installers.
Following the thread by Kris about SGN policy of not connecting to a receced meter box how many of you would ignore a receded box that gas pipe wasn't sleaved and sealed through rear and install new boiler to this supply.
Being seeing a lot more of these...
Very long day!
Out at this 12 year old heap the other day installed in a small cupboard about 200mm from floor.
Leak appeared to be coming from plate hex on left hand side. Struggling with access I drained and replaced the hex washers. Refilled to find drip still there.
Eventually sussed the...
Anyone know if possible to get the Alloy flue test point screw itself or got to purchase whole flue kit?
These strip very easily and some muppet Scot Gas Engineer has used firecement to cement it in place. :censored:
Attended the above 5 year old boiler for annual service.
Cleaned through the magna booster and brought pressure back upto 1.5bar and left boiler on as elderly customer feeling the cold.
Went on to service fire and as I went to turn boiler off to gas rate fire, noticed pressure was up at 2.5bar...
About time this 35 year old bit of junk went to the scrapheap; but anyone know where the spillage should be carried out on the fire?
No mention of it in MI's, so I assume it's at radiant canopy?
You proved the F/switch is functioning? You manually activated the F/switch to check it? Tested for resistance on operation?
Thermistor OK?
If so it points to the board.
Last job tonight.
2 year old compact he, fan running, aps proving, NTC/overheat stats OK, condi trap clear.
Switch on power, fan runs then goes to solid red, fan keeps running.
Is there anything else I may be missing before picking up a new board?