Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Boiler wont ignite after power off in the Boilers area at Plumbers Forums

Messages
20
I replaced a couple of TRVs earlier, and prior to starting I powered off the boiler (a Main Heat 15). Boiler is 7 months old, and never been isolated from the mains before today.

Once all the rads were bled, went to power on the boiler and now the pilot won't ignite. And the reset button doesn't do anything.

As a total novice I'm not intending messing with anything, but does anyone have any suggestions?

Thanks
 
Do you have the same issue for Hot Water and Central Heating? Or is Hot Water only ok? If it is both not functioning:

Is this operating on a sealed system?

If so:

Check that you have properly repressurised the system - it needs to at least 0.5bar

Check that you have power to the boiler.

Follow the reset procedure ( it is very simple) set out in the users manual - but you need to follow the precise process to ensure that the boiler has reset.

If it is only not operating on heating:

The motorised valve (s) would be my first point if call to find the fault.


Thereafter, if no success you need a Gas Safe Engineer to look at it
 
Hot water seems OK, that seems to be the only the pipe that gets hot. Though I can't see the pilot light, so that's confused me..!

Yeah, it's pressurised OK, I took it up to 1bar.
 
Think maybe I surpassed myself managing to replace the TRVs without flooding the house! Need to call in the experts to get it up and running in that case..
 
Is the pump running / can you hear it running
 
I bled all the rads. Didn't know I could bleed the pump tbh..? Or anything else.

Now's when I wish I'd left it alone.. Obviously don't know enough about the system, and thought I'd be clever and replace the rad valves. :(

So.. I just bled the pump. No air in that.
 
Last edited:
What motorised valve(s) do you have? You have opened the trv’s? Have you missed anything simple like the programmer? Also as per Craig, a photo at this point maybe good.
 
I've opened the TRVs, programmer is all ok, think I did all the obvious checks.

As for the motorised valve, I think it's a 3 port, but will add a pic of that too. I think that was playing up before today, as when I had hot water only on, the upstairs rads were heating up.

Hope the pics help..

IMG_20190608_220224.jpg


IMG_20190608_220235.jpg


IMG_20190608_220250.jpg
 
Always baffles me why installers are happy to replace the boiler and use the existing pump.
You could try turning your heating on, then using the speed selector on the side of the pump. By slightly turing it towards setting 2 but not actually going all the way, you'll hear the pump power off, do this for 10 seconds, then switch it back to 3 for 10 seconds, then off again and repeat for a fee minutes. If there is any air this could help dislodge it.
 
Yes you have a 3 port valve. Select heating and feel the pipe off the port labelled a, see if it gets hot. If not try heating and hot water together and see if it gets hot.
 
OK, so I've tried both suggestions, thanks Craig and cbw.

Pipe A doesn't get hot in either scenario. Also, I'm not sure of the relevance, but there's no resistance on the lever on bottom of the 3 port valve, whether the heating is on or off..
 
Is the pipe for B getting hot? If so note what cylinder stat is on then turn down to say 20 so it isolates that.

Have you adjusted the pump speed?

You have a bypass valve is that getting hot? Turn that off.
 
Is the pipe for B getting hot? If so note what cylinder stat is on then turn down to say 20 so it isolates that.

Have you adjusted the pump speed?

You have a bypass valve is that getting hot? Turn that off.

Pipe B. Nope.

I did try the pump at 2 setting for a while. No difference.

What's the bypass valve?
 
Might be worth mentioning, when I said

"As for the motorised valve, I think it's a 3 port, but will add a pic of that too. I think that was playing up before today, as when I had hot water on, the upstairs rads were heating up."

That's no longer happening. The rads don't heat up at all now..
 

Similar plumbing topics

A
Hi all, I have a viessmann vitoden 100 w...
Replies
0
Views
608
Abbie S
A
I'm sorry it's been difficult reading. Is this...
2
Replies
37
Views
4K
W
pcb issue so gas safe engy required sorry to say
Replies
1
Views
703
Nest setup hi John can you send me a pic of...
Replies
4
Views
4K
Jamone B
J
Back
Top