Hey friend, we're detecting that you're an American visitor and want to thank you for coming to PlumbersTalk.net - Here is a link to the American Plumbing Forum. Though if you post in any other forum from your computer / phone it'll be marked with a little american flag so that other users can help from your neck of the woods. We hope this helps. And thanks once again.

Discuss Capping off radiator above the floor, please advise. in the Central Heating Forum area at Plumbers Forums

Messages
37
Hey guys,

Quick question for all the I knowledgeable plumbers out there.
I need to remove one radiator which is first in line, as that room is being knocked down. Unfortunately I can’t cap off below the floor as it’s tilled. What’s the best course of action here?
Cap it off above the floor (will that not create air locks in those pipes?)
Join these two pipes together for continuity, but will I be able to get flow for the other two radiators down the line?

Thank you for any advise on this!
Lumen




A8748F0A-20E2-4A1C-9688-7251EA08D0A8.jpeg
 
Compression cap ends but surly it will cause a tripping hazard?

Also if it’s being knocked down the floor will have to be patched ?
 
Compression cap ends but surly it will cause a tripping hazard?

Also if it’s being knocked down the floor will have to be patched ?

Thank you for your reply Shaun.
The part where radiator was, will be boxed in, but I'm not sure what's best:
1. Cap the tails off 30-40cm above the floor (these will trap air?)
2. Join them for continuous flow, will this reduce the flow for the 2 radiators down the line?

Thanks,
Lumen
 
Can’t join them only option is to cap or lift the floor and remove the tees
 
Be fine you could put some air taps / vents on top but as your boxing it in no point as these won’t be accessible
 

Similar plumbing topics

Yeah, I did read this but I’ve inherited the...
Replies
8
Views
2K
You will need a check valve to stop reverse...
2 3
Replies
61
Views
7K
    • Like
Silly me! I must remember to check the date of...
Replies
5
Views
9K
I also have an i36 and just connected up the...
Replies
1
Views
3K
Tim Dug
T
Back
Top