So, does this indicate to you so far, that the behaviour is the same as with the HW enabled, ie that the system will still "never" need top up no matter how much air is vented?. If this is the case, then that would indicate that you are pulling air into the system and not venting residual air. If the PHE was causing the problem then you would expect the overall boiler pressure to gradually decay? now that its (the PHE) out of the picture.
Yes, that’s my understanding. I haven’t topped the system up since…I don’t know when!
Is it safe to assume that we’re pulling in air BELOW the towel rail?
I can fairly easily cap off the top floor. And run the system and see if that stops air coming in.
I can cap off the middle floor, just leaving the ground floor, too - but obviously trickier as it’s winter and house will be cold.
Any other suggestions welcome!